 SP1422 / BMS
Celab
Specification Input Voltage Input Frequency
Telephony 1000 Watts Uninterruptible Power Supply
230VAC, +15% - 10% Single Phase 47 to 63Hz EMC meets requirement of EN50081-1 & EN50082-1 15A Typical 54V to 58V (adjustable by potentiometer) 0-15A at 56VAC Load +/- 1%, Line +/- 0.2% In battery mode the output will be equal to the battery voltage, less 0.5V 100mV peak to peak, up to 20 MHz 4A DC >85% at full load -20C to +65C 0.02% per C
Emissions/Immunity Standards Inrush Current Output Voltage Output Current Range Output Regulation
Output Noise & Ripple Integrated battery management system. Designed for street cabinet applications. Non latching thermal protection. 15A output with separate 4A charging facility. Output voltage adjustable from 54V to 58V DC. Automatic and remote controlled battery condition testing. Comprehensive range of management alarms. Battery Charging Current Efficiency Operating Temperature Temperature Coefficient
Protective Features If ambient temperature exceeds 65C the power supply is protected by a non-latching thermal cut-out. Insulation - Input to Chassis 1500Vrms Insulation - Output to Chassis Insulation - Input to Output 3750Vrms Insulation - Output to Output Safety Standards Meets BSEN60950, LVD Compliant, CE marked. Current Limit Trip and restart, 20A +/- 1A Overvoltage Protection Low Battery Disconnect Auto Battery Test Feature
100Vrms 100Vrms
Trip and restart, 64V +/- 1V 42.5V +/- 0.5V The power supply will automatically load check the battery condition approximately every 20 days (or longer if required) for approximately 20 minutes to establish that the battery is `good'. If the battery voltage is below 47 volts, alarm 4 will operate.
Alarms The following 6 alarms are isolated and have a pair of contacts that can be factory configured open or closed in normal operation. Alarm 1: Input Mains Good Alarm 2: Output Voltage Good Alarm 3: Power Supply Good Alarm 4: Battery Good Alarm 5: Alarms 1 to 4 in Series Alarm 6: Thermal Cut Out Alarm Indicators Alarms 1 to 4 - Four Green LED's Mechanical Specification Size Weight Specification Note:
230mm x 230mm x 115mm Baseplate 280mm x 230mm 5kg For any requirements not specified above, please contact the sales department.
The SP1422 series has been specifically designed to reliably withstand the very high and low temperatures experienced in street cabinets. The battery management system enhances the life of the batteries by controlling the charging current and avoiding deep discharge. Regular battery test loading monitors battery health without risk of system failure.
Murata Power Solutions (Celab) Ltd, 25 Woolmer Way, Bordon, Hampshire, GU35 9QE
Tel: +44 (0) 1420 477011
Fax: +44 (0)1420 487476
www.murata-ps.com/celab


▲Up To Search▲   

 
Price & Availability of SP1422

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X